Scope Document · Medical Facility

DI Water Loop — PEX-A Repipe
Full Materials List

Inspection-compliant rebuild · Expansion PEX-A system · Non-metallic DI side

⚠️
Primary Inspection Failure — Replace Immediately SharkBite brass ball valve on DI line is non-compliant. Brass leaches copper/zinc into deionized water, contaminating the loop and violating lab-grade DI standards. All DI-side components must be non-metallic.
01 DI-Side Isolation Valve — Replace SharkBite
Part Number Item Brand Qty
TB1-375-01N
PVDF True Union Ball Valve ½" CRITICAL
Hayward TBH Series — PVDF body/ball, fully DI-rated, no metal wetted parts
Hayward 1
BV10PVDF5
PVDF Ball Valve ½" — Alt Option DI RATED
Asahi/America Type-21 — PVDF body, PTFE seats, socket or threaded ends
Asahi/America 1
02 PEX-A Tubing — Expansion System
Part Number Item Brand Qty
F1960500
AquaPEX Tubing ½" x 10ft PEX-A
Uponor/Wirsbo — ASTM F876/F877, expansion-compatible, NSF 61 certified
Uponor As needed
F1960750
AquaPEX Tubing ¾" x 10ft PEX-A
If existing supply line is ¾" — match existing diameter at supply
Uponor As needed
03 PEX-A Expansion Fittings — Brass (Potable Side Only)
Part Number Item Brand Qty
LF4507500
PEX-A Expansion Elbow ½" 90°
Uponor ProPEX LF brass — potable side only, not DI loop
Uponor 2–4
LF4517500
PEX-A Expansion Coupling ½"
Uponor ProPEX LF brass straight coupling
Uponor 2–4
LF4527500
PEX-A Expansion Tee ½"
Uponor ProPEX LF brass tee — for branching potable supply
Uponor 1–2
04 PEX-A Expansion Rings
Part Number Item Brand Qty
Q4500500
ProPEX Expansion Ring ½" (25-pack)
ASTM F1960 expansion rings for PEX-A — required for every fitting connection
Uponor 1 pack
Q4500750
ProPEX Expansion Ring ¾" (25-pack)
Only if ¾" tubing is used on supply side
Uponor 1 pack
05 Dual-Outlet Lab Faucet — Point of Use
Part Number Item Brand Qty
B-0892
Dual Outlet Lab Faucet — Deck Mount RECOMMENDED
T&S Brass — gooseneck + serrated hose outlet, single hole deck mount, ½" IPS inlets
T&S Brass 1
748-GN2ACP822
Lab Faucet with Side Hose Outlet
Chicago Faucets — gooseneck with integral side outlet, deck mount, lead-free
Chicago Faucets 1
06 Backflow Prevention
Part Number Item Brand Qty
9D-M2
Reduced Pressure Zone Backflow Preventer ½" REQUIRED
Watts 009-M2 or equivalent — required at DI supply tap connection per code
Watts 1
LF8-M3-QT
Dual Check Backflow Preventer ½" — Alt
Watts LF8 — if RPZ not required by local code, confirm with inspector
Watts 1
07 Pipe Supports & Hangers
Part Number Item Brand Qty
PHC-50
Plastic Pipe Hanger Clamp ½" (50-pack)
Non-metallic — every 32" horizontal run, every 4ft vertical per IPC
Oatey / Generic 1 pack
Insulation Sleeve ½" (if required)
Foam pipe insulation — prevents condensation on DI cold line near drain area
Armaflex / Generic As needed
08 Labeling — Code Required
Part Number Item Brand Qty
PSPVC-1/2
DI Water Pipe Label Tape ½" REQUIRED
"DI WATER" identification labels every 10ft and at all valves, tees, and changes of direction
Brady / Seton 1 roll

⚙ Field Notes & Verify Before Order